logo
Home page Contact
Home Contact
Electrical Transducers
T-IP Separately Powered Current Transducers
Model T-IP

T-IP Separately Powered Current Transducer

The T-IP current transducers convert an ac current input into an output signal which is proportional to the rectified arithmetic mean of the input.
Accurate measurement assumes a sinusoidal input waveform.
Power for the units is derived from an external source.


Basic Specifications:
InputRanges: 1A, 5A
Others on request, including a window option i.e. 3-5A
Burden: <0.1VA
Overload: 2xInom continuous, 20xInom for 3 seconds
Frequency: 50Hz, 60Hz
OutputsLoad independent dc current and voltage (others on request)
: 0 - 10mA dc <1500Ω load
: 0 - 20mA dc <750Ω load
: 4 - 20mA dc <750Ω load
: 0 - 5V dc >2kΩ load
: 0 - 10V dc >2kΩ load
Accuracy: Class 0.5 to IEC 60688
Range: 0 to 120% of nominal input
Power Supply: 24V, 110V, 230/240V, 400/415V ac ±20%, 1.5VA
: 24V dc ±20% or 110V/125V dc (88V-138V), 2W
IsolationGalvanic isolation between input, output circuit and auxiliary supply
Test voltage: 4kV 50Hz ac for 1 minute
TemperatureOperating: -10°C to +20°C to +50°C
EMC Compliance: AS/NZS 61000.6.3:2012
Dimensions
NZ flag
Carrel Electrade Limited
Proudly 100% New Zealand owned and operated.