Electrical Transducers
LP-VS Self Powered Voltage Transducer

Data sheet.

LP-VS, LP-VSX3 Self Powered Voltage Transducers

The LP-VS voltage transducer converts an ac voltage input into a dc output signal which is proportional to the rms calibrated rectified arithmetic mean of the input.
Accurate measurement assumes a sinusoidal input waveform.
Power for the unit is derived from the input signal.

The LP-VSX3 consists of three independent LP-VS circuits in a single case.

Ordering information: LP-VS(X3), input, output.
Example: LP-VS, input 0-250Vac, output 0-10mA


Basic Specifications:
InputAll system voltages to 500V
Burden: <2VA for 0 - 20mA and 0 - 10V versions
: <1.2VA for 0 - 10mA version
Overload: 1.2xVnom continuous, 1.5xVnom for 10 seconds
Frequency: 50Hz, 60Hz
OutputsLoad independent dc current and voltage
(others on request): 0 - 10mA dc <1500Ω load
: 0 - 20mA dc <750Ω load
: 0 - 5V dc >2kΩ load
: 0 - 10V dc >2kΩ load
Accuracy: Class 0.5 to IEC 60688
Range: 20 to 120% Vnom for current outputs
: 25 to 120% Vnom for voltage outputs
IsolationGalvanic isolation between input and output circuit
Test voltage: 4kV 50Hz ac for 1 minute
TemperatureOperating: 0°C to +23°C to +60°C
EMC Compliance: AS/NZS 61000.6.3:2012

DimensionsLP-VSLP-VSX3