Basic Specifications: |
Inputs | Current | : 1A or 5A (others on request) |
| Voltage | : All ac system voltages to 440 |
| Frequency | : 50Hz, 60Hz |
| Nominal range, power factor & | : 0.5 lead (+60°) to 1 (0°) to 0.5 lag (-60°) |
| phase angle (others on request) | : 1 ( 0°) to 0.5 lag (-60°) |
Output | Load independent dc current |
| (others on request) | : 0 to 10mA dc <1500Ω load |
| | : 0 to 20mA dc <750Ω load |
| | : 4 to 20mA dc <750Ω load |
Accuracy | | : Class 0.5 to IEC 60688 |
Power Supply | | : 24V, 110V, 230/240V ac ±20%, 1.5VA |
| | : 24V dc ±20% or 110V/125V dc (88V-138V), 2W |
Isolation | Galvanic isolation between inputs, output circuit and auxiliary supply |
| Test voltage | : 4kV 50Hz ac for 1 minute |
Temperature | Operating | : 0°C to +23°C to +60°C |
EMC Compliance | : AS/NZS 61000.6.3:2012 |